Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE OPERATIONAL REVIEW v.2
Permit Number - TF-FOP-0725-00935
Review Name: FIRE OPERATIONAL REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2025 | Fire Code Enforcement Fast | PENDING ASSIGNMENT | |||
| 07/16/2025 | Commercial Structural Express | REQUIRES RESUBMIT | COMMENTS: 1. Please make the necessary corrections enumerated below. a. The submitted structural documents is proposing to anchor the tent posts via screws/bolts to the hotel lawn/soil. Please submit the proper anchoring system that is conducive to this situation/condition such as staking or drum of water, etc. b. The structural documents is sealed/signed/dated by an Engineer from California. As you know the City of Tucson requires a Structural Engineer licensed in the State of Arizona. Please make this necessary correction. 3. Please resubmit. If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976 | ||
| 07/14/2025 | TFD Application Completeness Check Express | REVIEW COMPLETED |