Permit Number: TF-FCP-1222-00238
Parcel: 108254580

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1222-00238
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2023 Fire New Construction REQUIRES RESUBMIT Plans show you are using a 12v 7ah battery, but calculations show a 12x 12ah battery required. Provide symbol explanation for symbols provided.
Put the building square footage on the drawings.