Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-1222-00238
Parcel: 108254580

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1222-00238
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2023 Fire New Construction REQUIRES RESUBMIT Plans show you are using a 12v 7ah battery now (still) but standby time is now 11 hours and shall be 24 hours and 5 minutes in alarm.
Questions:

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/31/2023 TFD Application Completeness Check Express REVIEW COMPLETED