Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2023 Fire New Construction REQUIRES RESUBMIT You submitted an installation sheet. Fire alarm plans submitted do not show a current draw for the dialer and they are showing a different part number. Dialer appears to be panel powered technology and therefore, we will need updated battery calculations along with Data sheets to show the standby and alarm loads.

Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
01/26/2023 TFD Application Completeness Check Express REVIEW COMPLETED