Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-1222-00233
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2023 | Fire New Construction | REQUIRES RESUBMIT | You submitted an installation sheet. Fire alarm plans submitted do not show a current draw for the dialer and they are showing a different part number. Dialer appears to be panel powered technology and therefore, we will need updated battery calculations along with Data sheets to show the standby and alarm loads. Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
| 01/26/2023 | TFD Application Completeness Check Express | REVIEW COMPLETED |