Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-1222-00222
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2023 | Fire New Construction | REQUIRES RESUBMIT | Provide scope of work at dining (demo existing pendents throughout) Provide room identification and ceiling heights Show connections to existing piping, including size of existing piping, or relocation from existing pendent. Include type of pipe being used (sch. 40, dynathread, etc.) Refer to NFPA 13, 2016ed – 23.1.3 For questions or clarifications contact: patricia.shelton@tucsonaz.gov / 520.837.7082 |
||
| 12/20/2022 | TFD Application Completeness Check Express | REVIEW COMPLETED |