Permit Number: TF-FCP-1222-00214
Parcel: 137055990

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1222-00214
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2023 Fire New Construction REQUIRES RESUBMIT Provide hydraulic calculations of standpipe in accordance with NFPA 14, 2016ed. –7.8.1.2
Provide hydraulic signage in accordance with NFPA 14, 2016ed –6.8.3
Provide air vent in accordance with NFPA 13, 2016ed 7.1.5 Provide relief valves in accordance with NFPA 13, 2016ed 7.1.2.1
Please update/correct 4th floor Attic Calculation
Specify maximum spacing of “fast” response sprinklers clearly on plan
Note which sizes/locations are steel/cpvc Please reach out if you have any questions. Patricia.shelton@tucsonaz.gov 520.837.7082
01/17/2023 TFD Application Completeness Check REVIEW COMPLETED