02/03/2023 | Fire New Construction | REQUIRES RESUBMIT | Provide hydraulic calculations of standpipe in accordance with NFPA 14, 2016ed. –7.8.1.2 Provide hydraulic signage in accordance with NFPA 14, 2016ed –6.8.3 Provide air vent in accordance with NFPA 13, 2016ed 7.1.5 Provide relief valves in accordance with NFPA 13, 2016ed 7.1.2.1 Please update/correct 4th floor Attic Calculation Specify maximum spacing of “fast” response sprinklers clearly on plan Note which sizes/locations are steel/cpvc Please reach out if you have any questions. Patricia.shelton@tucsonaz.gov 520.837.7082 |
||
01/17/2023 | TFD Application Completeness Check | REVIEW COMPLETED |