Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-1222-00214
Parcel: 137055990

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1222-00214
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2023 Fire New Construction REQUIRES RESUBMIT Provide isolation valves for standpipes in accordance with NFPA 14, 2016 – 6.3.2.
Provide means for forward flow testing of the backflow in accordance with NFPA 13, 2016ed. –25.2.5.1
Provide hydraulic calculations of standpipe in accordance with NFPA 14, 2016ed. –7.8.1.2
Provide hydraulic signage in accordance with NFPA 14, 2016ed –6.8.3
Classification for Housekeeping/Laundry to be in accordance with NFPA 13, 2016ed. –5.3.1
Provide protection at Elevator in accordance with NFPA 13, 2016ed – 8.15.5
Provide hydraulic calculations for the remote area, area is permitted to be reduced in accordance with NFPA 13, 2016ed 11.2.3.2.3.1 and shall be increased in accordance with 11.2.3.4
Provide 4-head calculation NFPA 13, 2016ed 11.3.1.1
Correct upright spacing to exterior wall at 4th floor.
Provide air vent in accordance with NFPA 13, 2016ed 7.1.5
Provide relief valves in accordance with NFPA 13, 2016ed 7.1.2.1
Specify maximum spacing of “fast” response sprinklers clearly on plan
Note which sizes/locations are steel/cpvc
Please reach out if you have any questions.
Patricia.shelton@tucsonaz.gov
520.837.7082
12/20/2022 TFD Application Completeness Check REVIEW COMPLETED