Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TF-FCP-1125-00976
Parcel: 136130060

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1125-00976
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2025 Fire New Construction - Standard REQUIRES RESUBMIT Various areas exceed 130 sq. ft. spacing, update head spacing and min. end head condition. Clearly identify full-height walls/structural obstructions.
Questions: patricia.shelton@tucsonaz.gov
11/18/2025 TFD Application Completeness Check Express REVIEW COMPLETED