Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-1124-00981
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2024 | Fire New Construction | REQUIRES RESUBMIT | -Correct the nozzle height above the 4-burner range. Should be 34"-48". Drawing shows 24"-48". -The 1H nozzle over the dual burner has a max width of 12". Your appliance shows 18" width. john.vincent@tucsonaz.gov 5203495581 |
||
| 11/20/2024 | TFD Application Completeness Check Express | REVIEW COMPLETED |