Review Status: Approved
Review Details: FIRE CONSTRUCTION REVIEW v.4
Permit Number - TF-FCP-1124-00928
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2025 | Fire New Construction | REVIEW COMPLETED | 2024 IFC Section 903.4.3 Alarms. An approved audible and visual sprinkler water flow alarm device, located on the exterior of the building in an approved location, shall be connected to each automatic sprinkler system. Such sprinkler water flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. ( Every Fire Riser location) Inspector: Field verify. |
||