Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.4
Permit Number - TF-FCP-1123-01343
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/16/2024 | Fire New Construction | REQUIRES RESUBMIT | Hydraulic calculations provided show system supply pressures below 20 psi. Per Arizona Administrative Code R18-5-502 and Tucson Water Design Standard Manual Section 8-06.2.2: A potable water distribution system shall be designed to maintain and shall maintain a pressure of at least twenty pounds per square inch at ground level at all points in the distribution system under all conditions of flow, as required by AAC R18-5-502.B, Minimum Design Criteria. Questions: patricia.shelton@tucsonaz.gov |
||
02/13/2024 | TFD Application Completeness Check | REVIEW COMPLETED |