Permit Number: TF-FCP-1123-01343
Parcel: 141186610

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.4

Permit Number - TF-FCP-1123-01343
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2024 Fire New Construction REQUIRES RESUBMIT Hydraulic calculations provided show system supply pressures below 20 psi. Per Arizona Administrative Code R18-5-502 and Tucson Water Design Standard Manual Section 8-06.2.2: A potable water distribution system shall be designed to maintain and shall maintain a pressure of at least twenty pounds per square inch at ground level at all points in the distribution system under all conditions of flow, as required by AAC R18-5-502.B, Minimum Design Criteria.
Questions: patricia.shelton@tucsonaz.gov
02/13/2024 TFD Application Completeness Check REVIEW COMPLETED