Permit Number: TF-FCP-1123-01284
Parcel: 14036017B

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-1123-01284
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2023 Fire New Construction REQUIRES RESUBMIT -Remove all the building information from plan sheets. This includes all symbols (fire extinguisher, exiting travel distance, etc...). I only want the CO2 information.
-Include legend with CO2 devices.
-Include sequence of operations.
-Indicate if building has a fire alarm and if CO2 gas detection alarm will be interconnected and include in sequence of operations.
-Detection is required at every point of use. Explain where all your points of use are.
-Indicate where you are placing all your signage. Required at every point of use.
-Show all your notification devices on the plans.

I suggest hiring a licensed contractor that has experience with CO2 plan submittal and installation.
john.vincent@tucsonaz.gov
5203495581
11/16/2023 TFD Application Completeness Check Express REVIEW COMPLETED