Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-1123-01284
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/17/2023 | Fire New Construction | REQUIRES RESUBMIT | -Remove all the building information from plan sheets. This includes all symbols (fire extinguisher, exiting travel distance, etc...). I only want the CO2 information. -Include legend with CO2 devices. -Include sequence of operations. -Indicate if building has a fire alarm and if CO2 gas detection alarm will be interconnected and include in sequence of operations. -Detection is required at every point of use. Explain where all your points of use are. -Indicate where you are placing all your signage. Required at every point of use. -Show all your notification devices on the plans. I suggest hiring a licensed contractor that has experience with CO2 plan submittal and installation. john.vincent@tucsonaz.gov 5203495581 |
||
11/16/2023 | TFD Application Completeness Check | REVIEW COMPLETED |