Permit Number: TF-FCP-1123-01284
Parcel: 14036017B

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1123-01284
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2023 Fire New Construction REQUIRES RESUBMIT -Remove plan sheets that have nothing to do with CO2 submittal like the building envelope sheet.
-Do not use sheets from the building construction submittal that have building information, other permit numbers, architect stamps, etc...
-Include only the CO2 submittal information, including legends, data sheets, sequence of operations, etc...
-This is not an appropriate CO2 submittal. I suggest hiring a contractor that is experienced and licensed to install CO2 gas detection alarms.
john.vincentf@tucsonaz.gov
5203495581
11/06/2023 TFD Application Completeness Check Express REVIEW COMPLETED