Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.5
Permit Number - TF-FCP-1123-01284
Review Name: FIRE CONSTRUCTION REVIEW v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2024 | Fire New Construction | REQUIRES RESUBMIT | -Please indicate if the building has a building fire alarm or a dedicated function fire alarm for sprinkler monitoring. If so, the CO2 gas detection alarm will need to be interconnected to the fire alarm. john.vincent@tucsonaz.gov 5203495581 |
||
01/17/2024 | TFD Application Completeness Check | REVIEW COMPLETED |