Permit Number: TF-FCP-1123-01284
Parcel: 14036017B

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.4

Permit Number - TF-FCP-1123-01284
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2024 Fire New Construction REQUIRES RESUBMIT -Include sequence of operations.
-Indicate if building has a fire alarm and if CO2 gas detection alarm will be interconnected and include in sequence of operations.
-Show all your notification devices on the plans. You currently do not show any horn/strobes on the drawings.
I suggest hiring a licensed contractor that has experience with CO2 plan submittal and installation.