Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.4
Permit Number - TF-FCP-1123-01284
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2024 | Fire New Construction | REQUIRES RESUBMIT | -Include sequence of operations. -Indicate if building has a fire alarm and if CO2 gas detection alarm will be interconnected and include in sequence of operations. -Show all your notification devices on the plans. You currently do not show any horn/strobes on the drawings. I suggest hiring a licensed contractor that has experience with CO2 plan submittal and installation. john.vincent@tucsonaz.gov 5203495581 |
||