Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-1122-00115
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/09/2022 | Fire New Construction | REQUIRES RESUBMIT | -Indicate system is UL300 compliant -add nozzle on drawings above the 24x24 griddle -Include fusible link above stockpot appliance -Indicate if building has a fire alarm panel. It should since the building has fire sprinklers. If so, separate permit will be required for modification of the fire alarm. |
||