Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-1122-00010
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2022 | Fire New Construction | REQUIRES RESUBMIT | Provide coverage at closets in dwelling units in accordance with NFPA 12, 2016ed – 8.15.8. Provide protection at trash chute in accordance with NFPA 13, 2016ed – 22.15.2.2. Provide hydraulic calculations for dwelling units in accordance with NFPA 13, 2016ed – 11.3.1 For information on resubmittals see https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf Please reach out if you have any questions. Patricia Shelton Patricia.shelton@tucsonaz.gov 520.837.7082 |
||
| 11/22/2022 | TFD Application Completeness Check Express | REVIEW COMPLETED |