Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-1026-00697
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Under the 2018 IFC, Section 907.2 requires at least one manual pull station installed to initiate signals for water flow devices. *If no manual pull station is existing, please provide one and make changes to your plans. If one does exist, please show/notate it on the plans resubmitted in the "Sequence of Operations". 2018 IFC section 903.4.1 requires "Alarm", "Supervisory", and "Trouble" signals be distinctly different and automatically transmitted to an approved supervising station... *Please separate the different signals and show these on the "Sequence of Operations". For questions or concerns on these, please contact me. Ryan P Johnson Tucson Fire Department Fire Protection Plans Examiner (520)539-5370 Ryan.Johnson@Tucsonaz.gov |
||
| 11/02/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |