Permit Number: TF-FCP-1026-00669
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1026-00669
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2026 Fire New Construction - Standard REQUIRES RESUBMIT Provide coverage at new combustible exterior dining canopy in accordance with NFPA 13, 22ed. 9.3.19.1.
Provide location of full height walls in accordance with NFPA 13, 2022ed, 28.1.3 (I've identified some of the full height separations for you.)
Questions: patricia.shelton@tucsonaz.gov
10/22/2026 TFD Application Completeness Check Express REVIEW COMPLETED