Permit Number: TF-FCP-1026-00649
Parcel: 13316030G

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1026-00649
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2026 Fire New Construction - Standard REQUIRES RESUBMIT *Please submit "Scope of Project".
*Please submit floor plans showing what is existing vs what is new/replaced
*Please highlight which communicator (of the 3 in supplied spec sheet) is to be used.
*Please indicate number of each new device for this system to be added.
*Please submit battery calculations as per 2022 NFPA 10.6.7.2
For questions or concerns, please contact me.

Ryan P Johnson
Tucson Fire Department
Fire Protection Plans Examiner
(520)539-5370
Ryan.Johnson@Tucsonaz.gov
10/22/2026 TFD Application Completeness Check Express REVIEW COMPLETED