Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-1026-00638
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/09/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Per 2024 IFC 903.4.2 Monitoring. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved supervising station... *In the Sequence of Operations Matrix in submittal, please separate the "transmit signal to monitoring service" to reflect which signals are to be sent as "Trouble", "Supervisory" and "Alarm" signals. If you have questions or concerns on these, please reach out to me. Ryan P Johnson Tucson Fire Department Fire Protection Plans Examiner (520) 539-5370 Ryan.Johnson@Tucsonaz.gov |
||
| 10/06/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |