Permit Number: TF-FCP-1026-00638
Parcel: 14027051D

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-1026-00638
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2026 Fire New Construction - Standard REQUIRES RESUBMIT Per 2024 IFC 903.4.2 Monitoring. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to an approved supervising station...
*In the Sequence of Operations Matrix in submittal, please separate the "transmit signal to monitoring service" to reflect which signals are to be sent as "Trouble", "Supervisory" and "Alarm" signals.
If you have questions or concerns on these, please reach out to me.

Ryan P Johnson
Tucson Fire Department
Fire Protection Plans Examiner
(520) 539-5370
Ryan.Johnson@Tucsonaz.gov
10/06/2026 TFD Application Completeness Check Express REVIEW COMPLETED