Permit Number: TF-FCP-1024-00849
Parcel: 11504602D

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.5

Permit Number - TF-FCP-1024-00849
Review Name: FIRE CONSTRUCTION REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2024 Fire New Construction REQUIRES RESUBMIT Incomplete plans. Missing information.
-Equipment type/specs?
-What are you protecting?
-Is the plenum a V-bank with appliances that do not require protection? Your plenum detail shows a regular plenum. If it's a regular plenum, you're not showing plenum protection.
-Size of gas valve?
-Equipment drops with location/height requirements?
These plans are not complete.
-Submit your qualifications/certifications to inspect, test, maintenance and install this type of equipment.
john.vincent@tucsonaz.gov
5203495581
11/15/2024 TFD Application Completeness Check Express REVIEW COMPLETED