Permit Number: TF-FCP-1022-00004
Parcel: 137335950

Address:
1908 W NAVA DR

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-1022-00004
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2022 Fire New Construction REQUIRES RESUBMIT METER FLOW RATES PERMITTED BY TUCSON WATER:
https://www.tucsonaz.gov/files/water/docs/Signed_Meter_Sizing_Guidelines_MARCH_2020.pdf

8.2.1 Pipe Sizing. Piping shall be sized using hydraulic calculation procedures in accordance with NFPA 13.(NFPA 13, 2016, 23.4.1.6 Hydraulic calculations shall extend to the effective point of the water supply where the characteristics of the water supply are known. (I.E. CONNECTION TO CITY SUPPLY AT EXISTING UNDERGROUND MAIN))
6.6.5.1 Where a roof or deck is provided above, sprinklers shall be installed to protect attached exterior balconies, attached exterior decks, and ground floor patios serving dwelling units in buildings of Construction Type V.
*EXCEEDS 400sqft, PROVIDE DOCUMENTATION/REFERENCE PERMITTING EXPOSED CPVC INSTALLATION AT GARAGE
PROVIDE 2½" SINGLE SNOOT FDC W/KNOX CAP (SUPPLY TO 2½" CONNECTION CAN BE 1½") NFPA 13R 6.11
If you have any questions, please contact: Patricia Shelton patricia.shelton@tucsonaz.gov 520.837.7082
12/05/2022 TFD Application Completeness Check Express REVIEW COMPLETED