Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0926-00615
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2026 Fire New Construction - Standard REQUIRES RESUBMIT Submittal shows 3 different models of dialer.
*Please show which dialer is proposed in the resubmittal.
*If the chosen dialer does not contain it's own backup battery, please provide a battery calculation of the existing fire alarm panel proving the existing fire alarm backup battery will adequately power the new dialer in addition to the existing fire alarm system, including all of its devices, or specify the new backup battery to be installed.
If you have any questions or concerns with this, please reach out to me.