Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0926-00608
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2026 Fire New Construction - Standard REQUIRES RESUBMIT 2024 IBC 1010.2.11 (5,6), says...
5. Activation of the building fire alarm system, where provided, shall automatically unlock the electric lock, and the electric lock shall remain unlocked until the fire alarm system has been reset.
6. Activation of the building automatic sprinkler system or the fire detection system, where provided, shall automatically unlock the electric lock. The electric lock shall remain unlocked until the fire alarm system is reset.
In the Sequence of Operation on page FA-1, please deactivate magnetic door locks where the following occurs.
*Manual pull station activation
*Fire sprinkler water flow switch activation
*Kitchen hood fire suppression system activation

If you have and questions or concerns on these, please reach out to me.

Ryan P Johnson
Tucson Fire Department
Fire Protection Plans Examiner
(520)539-5370
Ryan.Johnson@Tucsonaz.gov
09/24/2026 TFD Application Completeness Check Express REVIEW COMPLETED