Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0926-00608
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | 2024 IBC 1010.2.11 (5,6), says... 5. Activation of the building fire alarm system, where provided, shall automatically unlock the electric lock, and the electric lock shall remain unlocked until the fire alarm system has been reset. 6. Activation of the building automatic sprinkler system or the fire detection system, where provided, shall automatically unlock the electric lock. The electric lock shall remain unlocked until the fire alarm system is reset. In the Sequence of Operation on page FA-1, please deactivate magnetic door locks where the following occurs. *Manual pull station activation *Fire sprinkler water flow switch activation *Kitchen hood fire suppression system activation If you have and questions or concerns on these, please reach out to me. Ryan P Johnson Tucson Fire Department Fire Protection Plans Examiner (520)539-5370 Ryan.Johnson@Tucsonaz.gov |
||
| 09/24/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |