Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.2
Permit Number - TF-FCP-0926-00606
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/21/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Thank you for providing dialer model, however, there is no back up battery specified for this installation. This unit will accommodate 12v batteries between 4Ah and 7Ah size. *Please provide the back up battery with spec sheet to be included in this installation. |
||
| 10/19/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |