Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0926-00606
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Submittal package provided contains specs for 2 different dialers. One of the dialers proposed uses the alarm panel's backup battery. The other dialer in the submittal has its own backup battery. *Please specify which of the 2 dialers is proposed for this project. *If the proposed dialer is the version without it's own backup battery, please provide battery calculations proving the fire alarm panel's existing backup battery will run the new dialer in addition to the existing fire alarm panel equipment. |
||