Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0926-00606
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/30/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Using the stated model of communicator (SLE-MAX2-CFBPS), the wrong current was used in the back up battery calc. Also, only the standby current was calculated. *Please update the battery calc to use the correct milliamp usage and include both standby and alarm currents. *Please include the back up battery specs for proposed back up battery to be installed in the dialer. |
||
| 10/27/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |