Permit Number: TF-FCP-0926-00606
Parcel: 13220003A

Address:
3401 E GAS RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0926-00606
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2026 Fire New Construction - Standard REQUIRES RESUBMIT Using the stated model of communicator (SLE-MAX2-CFBPS), the wrong current was used in the back up battery calc. Also, only the standby current was calculated.
*Please update the battery calc to use the correct milliamp usage and include both standby and alarm currents.
*Please include the back up battery specs for proposed back up battery to be installed in the dialer.
10/27/2026 TFD Application Completeness Check Express REVIEW COMPLETED