Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0926-00578
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Two communicators shown in provided submittal. *Please specify which communicator is to be used. If desired communicator does not have its own internal battery, *Please provide battery calculation showing existing panel backup battery will be large enough to run alarm panel functions plus this new communicator. |
||
| 09/15/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |