Permit Number: TF-FCP-0926-00578
Parcel: 10511061R

Address:
4500 N ORACLE RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.3

Permit Number - TF-FCP-0926-00578
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2026 Fire New Construction - Standard REQUIRES RESUBMIT Per NAPCO tech support, standby current draw for the SLE-MAX2-CFB-PS is figured using 101mA (or .101Ah). Per Tech support, the proper back up battery calc is figured using this number in the calc for both standby and alarm currents.
*Please refigure the back up battery calculation using these values as directed by 2024 NFPA 72 section 10 Exhibit 3 (Sample Battery Calculation) and attach to resubmittal.
After resubmitting backup battery calculation,
*Please submit the battery spec sheet showing battery (voltage and Ah)to be used.
11/05/2026 TFD Application Completeness Check Express REVIEW COMPLETED