Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0926-00578
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/05/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Per NAPCO tech support, standby current draw for the SLE-MAX2-CFB-PS is figured using 101mA (or .101Ah). Per Tech support, the proper back up battery calc is figured using this number in the calc for both standby and alarm currents. *Please refigure the back up battery calculation using these values as directed by 2024 NFPA 72 section 10 Exhibit 3 (Sample Battery Calculation) and attach to resubmittal. After resubmitting backup battery calculation, *Please submit the battery spec sheet showing battery (voltage and Ah)to be used. |
||
| 11/05/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |