Permit Number: TF-FCP-0926-00558
Parcel: 130144510

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0926-00558
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2026 Fire New Construction - Standard REQUIRES RESUBMIT Please provide hydrant flow test used, or model flow data from Tucson Water.
Provide req. min. 30gpm @ 15psi at booth duct sprinklers in accordance with NFPA 33, 2021ed. 9.5.1.6.
Questions: patricia.shelton@tucsonaz.gov
09/15/2026 TFD Application Completeness Check Express REVIEW COMPLETED