Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0926-00558
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Please provide hydrant flow test used, or model flow data from Tucson Water. Provide req. min. 30gpm @ 15psi at booth duct sprinklers in accordance with NFPA 33, 2021ed. 9.5.1.6. Questions: patricia.shelton@tucsonaz.gov |
||
| 09/15/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |