Permit Number: TF-FCP-0926-00552
Parcel: 12501001B

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0926-00552
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2026 Fire New Construction - Standard REQUIRES RESUBMIT Page FA-1 Fire Alarm Riser diagram shows Starlink SLE-MAX2-CFBPS communicator to be used, but Fire Alarm Symbols section shows LRR is Starlink SLE-MAX2-FIRE communicator, as does the battery calc on page FA-3.
*Please decide which panel to be used and modify the plans so all pages/sections are in agreement.

Battery calc also shows RA-6075R annunciator and UD-1000-UDACT that I'm failing to find anywhere else on the plans (in diagrams or text).
*Please remove from battery calcs (if not used) or add these to drawings/text (if used). (Or please point these out if I just missed them).
09/02/2026 TFD Application Completeness Check Express REVIEW COMPLETED