Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0926-00552
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | Page FA-1 Fire Alarm Riser diagram shows Starlink SLE-MAX2-CFBPS communicator to be used, but Fire Alarm Symbols section shows LRR is Starlink SLE-MAX2-FIRE communicator, as does the battery calc on page FA-3. *Please decide which panel to be used and modify the plans so all pages/sections are in agreement. Battery calc also shows RA-6075R annunciator and UD-1000-UDACT that I'm failing to find anywhere else on the plans (in diagrams or text). *Please remove from battery calcs (if not used) or add these to drawings/text (if used). (Or please point these out if I just missed them). |
||