Permit Number: TF-FCP-0925-00820
Parcel: 132131390

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0925-00820
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2026 Fire New Construction - Standard REQUIRES RESUBMIT Correct 4th floor anti-freeze system to meet the requirements of NFPA 13, 2022ed. 8.6. or remove the anti-freeze system.
Provide clarification on dashed piping (assumed steel)
Knox caps required at FDC and Standpipe hose outlets.
Questions: patricia.shelton@tucsonaz.gov
12/03/2025 TFD Application Completeness Check Express REVIEW COMPLETED