Permit Number: TF-FCP-0925-00794
Parcel: 12810082B

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0925-00794
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2025 Fire New Construction - Standard REQUIRES RESUBMIT -It appears you only have three detectors. Explain why you only need three and not four detectors.
-Correct the nozzle height measurements on the hood isometric and piping plan drawing. Sheet 2/3.
john.vincent@tucsonaz.gov
5203495581
09/18/2025 TFD Application Completeness Check Express REVIEW COMPLETED