09/29/2023 | Fire New Construction | REQUIRES RESUBMIT | -Include data sheets for emerson panel. -CO2 panel shall be interconnected to fire alarm panel. Sequence of operations shall state upon high alarm, general alarm will be activated and fire department notified. -Indicate if the soda machines have carbonators or if they are all located next to tank with BIB. You only show one CO2 detector next to tank. I am not familiar with this CO2 detection alarm. It isn't a product I have seen in our jurisdiction. Unknown if you will be able to interconnect this product with your building fire alarm. john.vincent@tucsonaz.gov 5203495581 |
||
09/27/2023 | TFD Application Completeness Check | REVIEW COMPLETED |