Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0923-01099
Parcel: 132131090

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.5

Permit Number - TF-FCP-0923-01099
Review Name: FIRE CONSTRUCTION REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2023 Fire New Construction REQUIRES RESUBMIT -Include data sheets for emerson panel.
-CO2 panel shall be interconnected to fire alarm panel. Sequence of operations shall state upon high alarm, general alarm will be activated and fire department notified.
-Indicate if the soda machines have carbonators or if they are all located next to tank with BIB. You only show one CO2 detector next to tank.

I am not familiar with this CO2 detection alarm. It isn't a product I have seen in our jurisdiction. Unknown if you will be able to interconnect this product with your building fire alarm.

john.vincent@tucsonaz.gov
5203495581
09/27/2023 TFD Application Completeness Check REVIEW COMPLETED