Permit Number: TF-FCP-0826-00541
Parcel: 136254120

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0826-00541
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2026 Fire New Construction - Standard REQUIRES RESUBMIT *Per 2024 IFC Section 903.4.2, Alarm, supervisory, and trouble signals shall be distinctly different and shall be automatically transmitted to an approved supervising station or, where approved by the fire code official...
*Please separate the alarm, supervisory, and trouble signals on the "sequence of operation" on page FA.1 to reflect this code requirement instead of sending a single generic signal that encompasses all of these.
*Please include in resubmittal a copy of the monitoring company's UL Certificate of Compliance (or similar).
*Also please note in the plans somewhere that when one 120VAC smoke alarm activates in an individual dwelling unit, all 120 VAC smoke alarms in the same dwelling unit shall activate per 2024 IFC 907.2.11.5
08/25/2026 TFD Application Completeness Check Express REVIEW COMPLETED