Permit Review Detail
Review Status: Approved
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0826-00531
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Approved
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2026 | Fire New Construction - Standard | REVIEW COMPLETED | Per NFPA 72 section 26.2.1.1 *Alarm signals initiated by manual fire alarm boxes, automatic fire detectors, waterflow from the automatic sprinkler system, or actuation of other fire suppression system (s) or equipment shall be treated as fire alarm signals. *Please update the "Operational Matrix" to reflect the ANSUL micro-switch activation to send "alarm" signals to the panel and to the supervising station, instead of a "trouble" signal. |
||
| 08/20/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |