Permit Number: TF-FCP-0826-00522
Parcel: 137055270

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0826-00522
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2026 Fire New Construction - Standard REQUIRES RESUBMIT Per 2018 IMC 606.4, Upon activation, the (duct) smoke detectors shall shut down all operational capabilities of the air distribution system in accordance with the listing and labeling of appliances used in the system.
*Please make this update to the sequence of operation matrix