Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0826-00522
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | *Please include in drawings what is existing (panel, smoke detectors, pull station, etc). Also include the existing back up battery size as I have no idea if what is being proposed will run as specified by the existing battery. Please include all the existing devices as well as the new devices (including duct detectors) in the battery calculation. | ||