Permit Number: TF-FCP-0826-00522
Parcel: 137055270

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0826-00522
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Fire New Construction - Standard REQUIRES RESUBMIT *Please include in drawings what is existing (panel, smoke detectors, pull station, etc). Also include the existing back up battery size as I have no idea if what is being proposed will run as specified by the existing battery. Please include all the existing devices as well as the new devices (including duct detectors) in the battery calculation.