Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0826-00521
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Fire New Construction - Standard REQUIRES RESUBMIT *New panel install is considered a new system, not a modification per 2024 IFC 1103.1. I went ahead and changed the permit from "Modification" to "New".

*In sequence of operation matrix, no condition is mentioned for a waterflow alarm. Please modify the sequence of operation matrix to reflect a waterflow alarm condition.