Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0826-00521
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2026 | Fire New Construction - Standard | REQUIRES RESUBMIT | *New panel install is considered a new system, not a modification per 2024 IFC 1103.1. I went ahead and changed the permit from "Modification" to "New". *In sequence of operation matrix, no condition is mentioned for a waterflow alarm. Please modify the sequence of operation matrix to reflect a waterflow alarm condition. |
||
| 08/18/2026 | TFD Application Completeness Check Express | REVIEW COMPLETED |