Permit Number: TF-FCP-0825-00680
Parcel: 133231430

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0825-00680
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Fire New Construction - Standard REQUIRES RESUBMIT -You referenced 2019 NFPA 13. COT/TFD has adopted the 2024 IFC (2022 NFPA 13). Make corrections to years referenced.
-Remove all information from drawings that do not pertain to the fire sprinklers.
-Describe the use of the space in the room utilizing the "small room rule."
-Provide new hanger detail.
john.vincent@tucsonaz.gov
5203495581
08/25/2025 TFD Application Completeness Check Express REVIEW COMPLETED