Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.3
Permit Number - TF-FCP-0825-00661
Review Name: FIRE CONSTRUCTION REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | The Underground Fire Line Plan should include the following (at a minimum): - Diameter, type, and length of all segments (4.1.3) - Indicate method and type of joint restraints (4.1.3) - Note indicating fire service underground to conform to NFPA 24 - Note minimum depth of bury to be _______. (30”, more if under high-weight traffic) (4.1.3) (10.4.2.2.2) - Note system to be tested at 200psi (or 50psi above street pressure) for 2 hours (10.4.2.2) - Note system to be flushed, and flush witnessed by TFD inspector (10.10.2.1) Please note inspectors will be looking at tracer wire, poly wrap of metallic fittings, etc at time of hydro. All code references refer to NFPA 24, 2022ed. Questions: patricia.shelton@tucsonaz.gov | ||