Permit Number: TF-FCP-0825-00646
Parcel: 14042075F

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0825-00646
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2025 Fire New Construction - Standard REQUIRES RESUBMIT Please update plans to comply with IFC 24. See TFD modification to IFC 24:
1103.1 Required construction. Is hereby AMENDED by ADDING the following paragraph:
A modification that increases the area protected by a fire protection system by fifty percent, or a fire alarm control panel replacement shall be considered a new installation, and the fire alarm system shall be brought to the current performance and installation standards in accordance with 907.5.
Questions: patricia.shelton@tucsonaz.gov
08/14/2025 TFD Application Completeness Check Express REVIEW COMPLETED