Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0825-00646
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2025 | Fire New Construction - Standard | REQUIRES RESUBMIT | Please update plans to comply with IFC 24. See TFD modification to IFC 24: 1103.1 Required construction. Is hereby AMENDED by ADDING the following paragraph: A modification that increases the area protected by a fire protection system by fifty percent, or a fire alarm control panel replacement shall be considered a new installation, and the fire alarm system shall be brought to the current performance and installation standards in accordance with 907.5. Questions: patricia.shelton@tucsonaz.gov |
||