Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0824-00646
Parcel: 13323193C

Address:
750 N KOLB RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0824-00646
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/06/2024 Fire New Construction REQUIRES RESUBMIT -Sheet KS-3, Tank 4&5. Piping diagram shows 290 fryer on tank #5, however, flow point calculation table on same sheet shows 290 fryer nozzle on tank #4.
-Since the appliance lineup is changing, provide/include the appropriate temp fusible links in the drawings.
thank you
john.vincent@tucsonaz.gov
5203495581
08/12/2024 TFD Application Completeness Check REVIEW COMPLETED