Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TF-FCP-0824-00641
Parcel: 10408075Q

Address:
4421 N ORACLE RD

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.1

Permit Number - TF-FCP-0824-00641
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2024 Fire New Construction REQUIRES RESUBMIT -Sequence of operations does not indicate a high CO2 alarm will transmit to a central station as a general alarm or CO2 alarm. There is a fire panel at this location which requires the CO2 gas detection alarm to be interconnected to the fire panel.
john.vincent@tucsonaz.gov
5203495581
08/08/2024 TFD Application Completeness Check REVIEW COMPLETED