Permit Number: TF-FCP-0824-00636
Parcel: 124050630

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.4

Permit Number - TF-FCP-0824-00636
Review Name: FIRE CONSTRUCTION REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/26/2024 Fire New Construction REQUIRES RESUBMIT -Plans were not reviewed. Submit a set of plans that are for the CO2 gas detection alarm only. Do not submit pages from the architectural plan set with additional information. This is a separate submittal that is specific to the CO2 gas detection alarm. I suggest hiring a licensed contractor that is familiar with submitting, installing and conducting acceptance testing for CO2 gas detection alarm.
john.vincent@tucsonaz.gov
5203495581
08/20/2024 TFD Application Completeness Check REVIEW COMPLETED