Permit Number: TF-FCP-0824-00630
Parcel: 12712267A

Review Status: Requires Resubmit

Review Details: FIRE CONSTRUCTION REVIEW v.2

Permit Number - TF-FCP-0824-00630
Review Name: FIRE CONSTRUCTION REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2024 Fire New Construction REQUIRES RESUBMIT -Sequence of operations does not indicate a high CO2 alarm will transmit to a central station as a general alarm or CO2 alarm. There is a fire panel at this location which requires the CO2 gas detection alarm to be interconnected to the fire panel. john.vincent@tucsonaz.gov 5203495581
08/12/2024 TFD Application Completeness Check REVIEW COMPLETED