Permit Review Detail
Review Status: Requires Resubmit
Review Details: FIRE CONSTRUCTION REVIEW v.1
Permit Number - TF-FCP-0823-01039
Review Name: FIRE CONSTRUCTION REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2023 | Fire New Construction | REQUIRES RESUBMIT | Update hydraulic calculations to provide coverage for actual spacing of (12x10.67) 25.6gpm. Reference NFPA 13, 2016ed. 23.4.4.2 for selection of remote area. Provide copy of model fire flow data or remove white out from page. | ||
| 08/29/2023 | TFD Application Completeness Check Express | REVIEW COMPLETED |